Our fixed installations use any combination of 3 cooler: a downwards, sideways and top discharge unit.
Which unit we choose will dependend entirely on location and will be affected, for example by:
Cooler units can be supplied without the fan as a "wet box" to act as a pre-cooler for an existing system or in instances where a higher duty fan is required. Air flow resistance in this configuration is low: for example a down-discharge unit has a resistance of 50 Pa at 14,000m³/hr.
Minimum pressure 1 bar; maximum 7 bar
Cooler sump capacity is 23 litres.
The cooler is supplied with a 300mm flexible connector pipe with isolation valve and finishing in a 15mm compression fitting.

240V 50Hz. The unit draws 12 amps at startup and 8 amps when running. External isolator fitted as standard.
Minimum capacity of 2000l/hour required to an appropriate drain point that complies with local water regulations.
| Component | Specification |
| Circulation Pump | 50W Centrifugal |
| Dimensions | Height 950, Length 1170mm, Width 1170mm, Volume 1.3m³ |
| Duct Size (Down Discharge) | Length 645mm x Width 645mm |
| Weight | Dry 55kg; Operating (wet) 92kg |
| Warranty | 2 years parts only, dependent on cooler being installed and maintained by authorised installer |
| Control | Standard wall control supplied with cooler with 30m cable incorporating spare cores for timer, alarm, thermostat & humidistat. |
| Fan | 1.5kW axial |
If you wish to find out more about: